Category: Media

  • Gas Regulations.

    Gas Regulations.

    Boiler regulations are there to protect more than just the gas supply.

    If a funded standalone boiler installation is being installed and is not part of a funded government backed scheme , then this may not fall under the current PAS and will only need to follow gas safe and manufacturers instructions, unless a package that includes insulation has been developed as part of a funded scheme, this may change due to future legislation.

    Installation Requirements and regulations.

    Since 15 June 2022, fitting a magnetic filter is mandatory in the UK when replacing a boiler or installing a new central heating system. This requirement falls under Building Regulations Part L (Conservation of fuel and power) and complies with the BS 7593:2019 code of practice
    While there is no specific UK building regulation that mandates a shock arrestor simply because a boiler is close to a water meter, it is frequently required to meet Water Supply (Water Fittings) Regulations regarding pressure, and it is a strict requirement by most boiler manufacturers (MI – Manufacturer Instructions) to protect against damage.
    The homeowner should provide measures as a minimum for their own safety and so that gas engineers can work in a safe environment. There should be a permanent means of safe access to the appliance. For example, this could be a permanently fixed retractable ladder to enter and exit the loft, with a safety guard around the loft access, which should be secured to the building’s fabric. The strength and design of the ladder should be such as to maintain safety. There should also be adequate fixed lighting.
    Section 5 (specifically paragraph 5.20) of the Approved Document L, Volume 1: Dwellings, 2021 edition (incorporating 2023 amendments.
    The Gas Safety (Installation and Use) Regulations 1998 (GSIUR), specifically regarding safe installation and discharge. These must also comply with the Pressure Systems Safety Regulations 2000 (PSSR)
    Condensate pipework is primarily regulated by BS 6798:2014 (Specification for installation and maintenance of gas-fired boilers), alongside UK Building Regulations and manufacturer instructions.
    The primary regulation for boiler programmers in the UK is Part L of the Building Regulations (Conservation of fuel and power), which was significantly updated in 2018 (Boiler Plus) and again in 2022 to improve energy efficiency
    Boiler interlock, which ensures the boiler and pump turn off when there is no demand for heating or hot water, is required under Part L of the Building Regulations in England and Wales, specifically enforced through the Boiler Plus standards introduced in April 2018. It is mandatory for all new gas and oil boiler installations in existing homes to have this control functionality to improve energy efficiency.
    Boiler pipework insulation in the UK is governed by Building Regulations Approved Document L (Conservation of Fuel and Power), specifically requiring compliance with BS 5422:2023. All primary circulation pipes for heating and hot water, including those in voids, must be insulated to reduce energy loss.
    Gas boiler installation is governed primarily by the Gas Safety (Installation and Use) Regulations 1998 (GSIUR), which legally mandate that only a Gas Safe registered engineer can install, repair, or maintain gas appliances.
    Flues in voids must allow for inspection along their entire length to comply with the Gas Safety (Installation and Use) Regulations 1998 (GSIUR 26(9)) and Technical Bulletin 008.
    Boiler condensate removal is primarily regulated by BS 6798:2014 (Specification for installation of gas-fired boilers) in the UK, which dictates that condensate must be discharged to an internal foul water system to prevent freezing. If external termination is required, pipes must be at least 30mm diameter and insulated.
    While the “Benchmark Scheme” itself is an industry-led code of practice, it is recognized by the government as a means of demonstrating compliance with mandatory Building Regulations. Unfilled benchmarks can void warranty and class the installation as Uncommissioned and unsafe.
    Gas flue regulations in the UK (Building Regulations Approved Document J, BS 5440) require terminals to be at least 300mm–600mm away from doors/windows and 2m below roof levels to prevent exhaust reentry. Concealed flues in voids must have inspection hatches for safety checks
  • Awaab’s Law

    Awaab’s Law

    Awaab’s Law: What Social Housing Tenants & Landlords Need to Know (And Why It Matters for Damp, Mould & Energy Efficiency)

    From October 2025, a major new rule comes into force for social housing in England: Awaab’s Law.
    It’s one of the biggest changes to tenant safety and housing quality in years, and it was introduced after the tragic death of two year old Awaab Ishak, who died in 2020 from prolonged exposure to mould in his home.

    This Law is designed to make sure this never happens again.

    In this post, we cover what the new law means, how it affects landlords, what tenants can expect, and why it directly links to issues we discuss regularly.

    What Is Awaab’s Law?

    Awaab’s Law is a legal requirement for social landlords (housing associations and councils) to respond quickly when tenants report damp, mould, or other serious hazards. It Should be rolled out to private landlords in the near future.

    It introduces strict, legally enforceable timeframes for.

    • Investigating reported hazards,
    • Making the property safe,
    • Providing written updates to tenants,
    • Offering alternative accommodation if necessary,

    For decades, damp and mould issues were too often dismissed as “lifestyle problems”.
    Awaab’s Law formally ends that.

    The Key issues social Landlords Must adhere to are.

    1. Damp & Mould Hazards.

    2. Emergency Hazards.

    These key issues will be automatically written into all social housing tenancy agreements.
    If a landlord doesn’t comply, tenants can take legal action or escalate complaints to the Housing Ombudsman.

    Why Awaab’s Law Matters for Energy-Efficiency & Retrofit.

    • condensation
    • ventilation problems
    • cold bridging
    • poor insulation
    • underheating
    • moisture build-up

    Awaab’s Law is a game-changer because damp and mould aren’t just health hazards, they’re signs of a home that isn’t performing properly.

    Damp & mould most commonly occur when:

    • insulation is poor.
    • ventilation is inadequate.
    • heating is inconsistent or too expensive.
    • building fabric is damaged.
    • retrofit work was done badly.
    • extractor fans don’t work.
    • air can’t escape after insulation works.

    Better insulation + better ventilation = fewer mould cases.

    Awaab’s Law may push more landlords to:

    • upgrade ventilation systems to meet households needs.
    • improve insulation correctly and professionally
    • fix construction defects timely.
    • install appropriate heating that can hopefully be afforded by tenants.
    • ensure post-retrofit checks are done correctly by qualified personnel.

    Healthy homes are energy-efficient homes and vice-versa.

    What Tenants Should Do If They Spot Damp or Mould.

    If you live in social housing (council or housing association), you have new legal protection.

    You should:

    1. Report the issue formally. (email is best)
    2. Include photos and dates. (try to use a GPS camera, lots of free ones on online)
    3. Keep copies of everything.
    4. Allow the landlord access for inspections. (a good landlord will always have your best interest at heart, so try to oblige when they request access)

    If they don’t meet the Awaab’s Law time frames, you can escalate:

    Social landlords must now:

    • Have a damp & mould action plan.
    • Update repairs procedures
    • Train staff on moisture, ventilation, and building fabric
    • Monitor high-risk properties.
    • Keep written communication with tenants.
    • Ensure compliance with the new timeframes.

    This law requires a shift from “reactive repairs” to proactive housing management.

    The law is going to change and will add phases over the years, including,

    Phase 2 (2026–2027)

    Will likely expand to include:

    • Managing excess heat and cold.
    • Identification of electrical/fire risks.
    • Identification of structural problems.
    • Identification of hygiene hazards.

    This will raise the baseline standard for social housing significantly.

    Whether you’re a tenant, a homeowner, or researching Warmhomes/BUS/solar/insulation upgrades, the message is the same:

    Awaab’s Law highlights that:

    • Ventilation is essential
    • Insulation must be done properly
    • Properties need regular inspection
    • Moisture can’t be ignored
    • Housing quality is a health issue

  • Why Putting Customers First Shouldn’t Need a new Charter.

    Why Putting Customers First Shouldn’t Need a new Charter.

    Why Putting Customers First Shouldn’t Need a new Charter.

    Consumer protection in the UK is built on clear principles: fair trading, honest communication, and accountability. Trading Standards exist to uphold these rights, stepping in where businesses fail to act responsibly or where consumers are misled, overcharged, or treated unfairly. Their role is vital — but in an ideal world, they shouldn’t need to be involved in most everyday installations.

    Putting the customer first is not optional, it’s fundamental.

    Whether it be government funded or a private job, the care, and quality should be the same.
    Clear advice, realistic expectations, fair pricing, and doing the job properly should be standard practice in any trade, not something that needs reinforcing through updated charters and commitments.

    That’s why it’s slightly disheartening that schemes now require formal customer commitments to spell out what should already be in place. Consumer protection, transparency, and quality should be embedded as default requirements — not corrective measures after poor behaviour has become widespread.

    Ultimately, the goal should be simple:

    If those principles were consistently followed, fewer charters would be needed — and Trading Standards could focus on the truly bad actors, rather than failures of basic professionalism.

    Customer first thinking shouldn’t be a policy. It should be the culture of every business.

  • Whats Behind Mold and Condensation?

    Whats Behind Mold and Condensation?

    A warm, energy-efficient home only works properly when:
    insulation + heating + ventilation all work together.

    Cooking, showering, drying clothes and even breathing all add water vapour into the air.
    When this warm, moist air hits colder surfaces, it turns into condensation.

    If this moisture isn’t controlled, it can lead to mould growth.

    The Balance!

    • Too little ventilation = Moisture builds up → Condensation → Mould.
    • Too much ventilation = Heat is lost → Home feels cold.
    • Just right, Fresh air in = moisture out → Healthy home.

    How retrofit changes our home..

    With insulation and heating upgrades, your home now:

    • Holds heat better.
    • Is more airtight.
    • Needs managed and controlled ventilation, not accidental draughts.

    Think of it like wearing a warm coat, you still need to adjust the zip if you gret too warm..

    USING YOUR HOME CORRECTLY

    ✔ Open trickle vents or background vents.
    ✔ Use extractor fans when cooking or showering.
    ✔ Keep internal doors slightly open for airflow.
    ✔ Heat your home steadily (not on/off extremes).
    ✔ Avoid drying clothes indoors without ventilation.

    Understanding what goes on behind the scenes!

    Interstitial condensation is the formation of liquid water inside the hidden, internal layers of a building’s structure (walls, roofs, or floors) rather than on the visible surface. It occurs when warm, moist air penetrates the building envelope and reaches a cold surface (dew point) within insulation, brickwork, or behind cladding, often causing structural damage, rot, and reduced insulation performance. This is extremely important when internal wall insulation is installed as any failures in design will cause weak points, This allows moisture to venture behind and out of sight. This is why ventilation and attention to design and detail is paramount.

    What is Relative Humidity (RH)?

    RH tells you how much moisture is in the air.
    Take a look at the video below to show you what 100% humidity is like.

    • Below 40% → Air too dry.
    • 40–60% → Ideal range .
    • Above 60% → Risk of condensation & mould .

    A simple humidity monitor can help you stay in the safe zone.

    Signs to watch out for.

    • Water droplets on windows.
    • Musty smells.
    • Black spots on walls or ceilings.
    • Damp patches behind furniture.

    What is the Dew Point?

    The dew point is the temperature to which air must cool down to become fully saturated with water vapor and start producing dew, fog, or condensation. A higher dew point means more moisture in the air, making it feel stickier and more uncomfortable outside.